The SL250 Series switchover system is designed with Gentec’s R21SL Series pressure reducing regulators to provide an uninterrupted supply of gas from two high pressure banks. The system will automatically switch from the primary bank to the reserve bank without flow interruptions. An optional audible and visual remote alarm is available to power the indicator lights for the system.
Features
• Based on R21SL Series Regulator
• Metal-to-Metal diaphragm seals
• Components enclosed for extra protection
• Priority knob with arrow indicator
• Built-in relief valve
• Check valves on pigtails
• Capable for visual alarm
• Regulators and piping are tested for pressure and leakage
• Wall mounts optional
EX: SL250 | A | 100 | D | 2L | 2R | C350 | S | 1 |
SERIES | LAYOUT | MAX. OUTLET PRESSURE | OUTLET CONNECTION | LEFT STATIONS | RIGHT STATIONS | INLET CONNECTIONS | PIGTAIL | OPTIONS |
SL250 | A: 12” standard | 50 psig | D: Diaphragm Valve | 1 | 1 | C320: CGA320 | S: 316L | 1: Alarm |
| 100 psig | No Options: Blank | 2 | 2 | C350: CGA350 | T: Teflon | 3: Flashback arrestors | |
150 psig | Leave blank for no options | 3 | 3 | C540: CGA540 |
| 4: Filter | ||
4 | 4 | C580: CGA580 | No options: Blank | |||||
5 | 5 | C590: CGA590 | Can choose multiple options | |||||
Blank for box only | Blank for box only | For other connections, please contact Gentec. |
|
• Maximum inlet pressure: 3000 psig
• Working temperature: -40˚F - 140˚F (-40˚C - 60˚C)
• Pipe: 1/2” seamless stainless steel (BA grade)
• Flow rate: see flow chart
• Regulators leak rate: 2 x 10-9 scc/sec Helium
• Body, diaphragm, filter: 316L
• Bonnet: 304
• Seat: PCTFE
• Biotech
• Research Laboratories
• Gas Chromatography